A water treatment train is generally divided into four main phases (preliminary, primary, secondary, and tertiary). In practice, the configuration varies considerably from one facility to another, depending on the infrastructure and the applicable discharge standards. Traditional plants usually rely on large, aerated ponds, whereas modern technologies enable a more compact and efficient treatment. Although these categories serve as general guidelines that are adapted on a case-by-case basis, understanding the specific purpose of each phase remains essential.

When the wastewater arrives at the treatment centre, it contains a lot of large objects (disposable wipes, plastics) and debris (such as sand and gravel from roads). These coarse materials must be removed to protect the equipment downstream in the treatment process. This phase is known as preliminary treatment, and in some municipalities, it is the only level of treatment achieved.
The most commonly used technologies are:
The pretreated water then proceeds to the primary treatment. The purpose of this phase is to remove suspended solids and a part of the organic load (insoluble COD) through a physicochemical process. As the name implies, such a process typically involves the addition of chemicals (coagulants and polymers) and/or a physical effect that enables better separation and settling of the flocs.
The technologies that are typically used are:
This step is crucial in the water treatment process. At Aquasan, we have the knowledge and expertise to optimize physicochemical treatment. In fact, choosing the right coagulant and polymer can have a major impact on improving the quality of clarified water while significantly reducing the volume of sludge produced. For more details on this phase of the treatment, please see our article on the fundamentals of coagulation and flocculation.
Secondary treatment is also known as the biological treatment. The purpose of this stage is to provide an environment that promotes the growth of bacteria naturally present in the water, allowing them to consume the dissolved organic matter. Therefore, a minimum level of biological oxygen demand (BOD) is required in the wastewater to sustain this biological process.
The secondary treatment can be aerobic (in the presence of oxygen) or anaerobic (without oxygen). For aerobic treatment, activated sludge systems are the most common. Moving-bed bioreactors (MBBRs) are also used, in which biomass grows on suspended carriers, thereby eliminating the need for sludge recirculation. Anaerobic digesters are another method that provides an effective secondary treatment while allowing for the utilization of the biogas that is produced.
Temperature, dissolved oxygen levels in aerobic treatment processes, and the nutrient ratio (carbon, nitrogen, phosphorus) are critical factors at this stage and must be carefully monitored. For a more detailed explanation of the importance of nutrients, see our article on optimizing activated sludge systems – the significance of C:N:P and how to maintain it.
A sedimentation stage or a second physicochemical treatment is often required downstream to remove suspended biological biomass. For this phase, Aquasan’s expertise can help you determine which products to use to effectively separate the biomass.
For many water treatment plants, the tertiary treatment phase is necessary to comply with strict discharge standards set by the environmental authorities. Tertiary treatment can be divided into three main categories: disinfection to eliminate pathogens (using UV lamps or ozone injections), nutrient removal (particularly phosphate removal), and advanced filtration (sand filtration, ultrafiltration membranes, or activated carbon) to capture residual micropollutants.
Phosphate removal, often achieved through chemical precipitation using metal salts, is a crucial step when water is discharged into the environment, as excessive phosphorus loads promote the proliferation of algae and cyanobacteria, leading to rapid eutrophication of waterways. The following article will help you better understand this process: Chemical Phosphorus Removal from Wastewater
At Aquasan, our experts can come directly to you to help you optimize your treatment with a personalized approach, regardless of the treatment phase.